The electric reactive power Q (kVar) is taken from the grid and used to generate the electromagnetic field necessary for the operation of induction motors and transformers. This power cannot be transformed into a different form of energy, but it only flows idly between sources and takeoffs of alternating current.
Instead of transmitting reactive power over long distances through the transmission grid, it can be produced locally (e.g. at an industrial plant or in a power distribution location). This is referred to as reactive power compensation and is often done by installing capacitors and capacitor banks. Reactive power compensation and the use of capacitor banks delivers real technical, economic and ecological benefits. Using a properly selected capacitor bank for the customer means that additional appliances can be installed without having to replace the power transformer. However, the most important economic factor is the lack of charges for reactive energy consumption, as electricity suppliers use additional charges to compensate for losses incurred as a result of reactive power transmission (when power factor tg ϕ at customer's industrial plant is higher than 0 .4 or cos ϕ is lower than 0 .93);

The technical and economic aspects are also very important for the electricity supplier, since the power to be generated in the power plant and then sent to the industrial plant is decreased. As described above, the use of capacitor banks for inductive reactive power compensation is aimed at reducing losses in transmission grids, reducing inductive power consumption and, consequently, reducing electricity bills.
There are many methods for determining the reactive power values. A quick method of selecting the capacitor bank power involves using an electricity bill. This should be done when the plant load was at the target level during the invoiced period. The bill also gives tg ϕ – maximum in a given billing period.

Non-choke capacitor bank specifications

Basic type: BKZN
Nominal power of a single rack: 2,5 do 125 kVAr
Nominal power of a cabinet set: 7,5 do 300 kVAr
Nominal voltage: 3x400 V - 50 Hz 
Maximum allowable voltage: 520 V (capacitor)
Harmonics: THDU < 3% & THDI < 10% < SH/ST ≤ 25%
Loss factor: 2 W / kVAr
Operating temperature range: -10°C / +45°C
Storage temperature: od -20 do +60°C
Cabinet dimensions (W x D x H): 600x500x1400mm
Rack dimensions (W x D x H): 580x400x248mm
Compilant with: IEC 61439-1 i 2

Capacitor banks cabinets with automatic power control without chokes
Type Catalogue number Bank power [kVAr] Degrees [kVAr] Cabinet dimensions [mm] (H x W x D) Number of units
BKZN-7,5 WN-1464-01-01-011 7.5 (3x2.5) 1400 x 600 x 500 3
BKZN-10 WN-1464-01-02-011 10
(2x2.5)+(1x5) 1400 x 600 x 500 3
BKZN-15 WN-1464-01-03-011 15 (1x2.5)+(1x5)+(1x7.5) 1400 x 600 x 500 3
BKZN-20 WN-1464-01-04-011 20 (1x2.5)+(1x5)+(1x12.5) 1400 x 600 x 500 3
BKZN-25 WN-1464-01-05-011 25 (1x5)+(2x10) 1400 x 600 x 500 3
BKZN-30 WN-1464-01-06-011 30 (3x10) 1400 x 600 x 500 3
BKZN-35 WN-1464-01-07-011 35 (1x5)+(1x7.5)+(1x10)+(1x12.5) 1400 x 600 x 500 4
BKZN-40 WN-1464-01-08-011 40 (1x7.5)+(2x10)+(1x12.5) 1400 x 600 x 500 4
BKZN-45 WN-1464-01-09-011 45 (2x10)+(2x12.5) 1400 x 600 x 500 4
BKZN-50 WN-1464-01-10-011 50 (2x12.5)+(1x25) 1400 x 600 x 500 3
BKZN-55 WN-1464-01-11-011 55 (1x7.5)+(1x10)+(1x12.5)+(1x25) 1400 x 600 x 500 4
BKZN-60 WN-1464-01-12-011 60 (1x10)+(2x12.5)+(1x25) 1400 x 600 x 500 4
BKZN-62,5 WN-1464-01-13-011 62.5 (3x12.5)+(1x25) 1400 x 600 x 500 4
BKZN-70 WN-1464-01-14-011 70 (1x7.5)+(1x12.5)+(2x25) 1400 x 600 x 500 4
BKZN-75 WN-1464-01-15-011 75 (3x25) 1400 x 600 x 500 3
BKZN-87,5 WN-1464-01-16-011 87.5 (1x12.5)+(3x25) 1400 x 600 x 500 4
BKZN-100 WN-1464-01-17-011 100 (2x25)+(1x50) 1400 x 600 x 500 3
BKZN-112,5 WN-1464-01-18-011 112.5 (1x12.5)+(2x25)+(1x50) 1400 x 600 x 500 4
BKZN-125 WN-1464-01-19-011 125 (1x2)5+(2x50) 1400 x 600 x 500 3
BKZN-150 WN-1464-01-20-011 150 (1x25)+(1x50)+(1x75) 1400 x 600 x 500 3
BKZN-175 WN-1464-01-21-011 175 (1x25)+(3x50) 1400 x 600 x 500 4
BKZN-200 WN-1464-01-22-011 200 (1x25)+(2x50)+(1x75) 1400 x 600 x 500 4
BKZN-225 WN-1464-01-23-011 225 (1x25)+(1x50)+(2x75) 1400 x 600 x 500 4
BKZN-250 WN-1464-01-24-011 250 (2x50)+(2x75) 1400 x 600 x 500 4
BKZN-275 WN-1464-01-25-011 275 (1x50)+(3x75) 1400 x 600 x 500 4
BKZN-300 WN-1464-01-26-011 300 (4x75) 1400 x 600 x 500 4
BKZN-65 WN-1464-01-27-011 65 (2x12.5)+(1x25)+15 1400 x 600 x 500 4
BKZN-90 WN-1464-01-28-011 90 (1x15)+(3x25) 1400 x 600 x 500 4
 

Choke capacitor bank specifications

Basic type: BKZN
Nominal power of a single rack: 2.5 do 125 kVAr
Nominal power of a cabinet set: 7.5 do 300 kVAr
Nominal voltage: 3x400 V - 50 Hz 
Maximum allowable voltage: 520 V (capacitor)
Harmonics: THDU < 6% & THDI < 40% < SH/ST ≤ 50%
Loss factor: 6 W / kVAr
Opening temperature range: -10°C / +45°C
Storage temperature: od -20 do +60°C
Cabinet dimensions (W x D x H): 800x500x1600mm
Rack dimensions (W x D x H.): 700x458x325mm
Compilant with: IEC 61439-1 and 2

Capacitor banks cabinets with automatic power control with chokes
Type Catalogue number Bank power [kVAr] Degrees [kVAr] Cabinet dimensions [mm] (H x W x D) Number of units
BKDZN-7,5 WN-1465-03-01-011 7.5 (3x2.5) 1600 x 800 x 500 3
BKDZN-10 WN-1465-03-02-011 10
(2x2.5)+(1x5) 1600 x 800 x 500 3
BKDZN-15 WN-1465-03-03-011 15 (1x2.5)+(1x5)+(1x7.5) 1600 x 800 x 500 3
BKDZN-20 WN-1465-03-04-011 20 (1x2.5)+(1x5)+(1x12.5) 1600 x 800 x 500 3
BKDZN-25 WN-1465-03-05-011 25 (1x5)+(2x10) 1600 x 800 x 500 3
BKDZN-30 WN-1465-03-06-011 30 (3x10) 1600 x 800 x 500 3
BKDZN-35 WN-1465-03-07-011 35 (1x5)+(1x7.5)+(1x10)+(1x12.5) 1900 x 800 x 500 4
BKDZN-40 WN-1465-03-08-011 40 (1x7.5)+(2x10)+(1x12.5) 1900 x 800 x 500 4
BKDZN-45 WN-1465-03-09-011 45 (2x10)+(2x12.5) 1900 x 800 x 500 4
BKDZN-50 WN-1465-03-10-011 50 (2x12.5)+(1x25) 1600 x 800 x 500 3
BKDZN-55 WN-1465-03-11-011 55 (1x7.5)+(1x10)+(1x12.5)+(1x25) 1900 x 800 x 500 4
BKDZN-60 WN-1465-03-12-011 60 (1x10)+(2x12.5)+(1x25) 1900 x 800 x 500 4
BKDZN-62,5 WN-1465-03-13-011 62.5 (3x12.5)+(1x25) 1900 x 800 x 500 4
BKDZN-70 WN-1465-03-14-011 70 (1x7.5)+(1x12.5)+(2x25) 1900 x 800 x 500 4
BKDZN-75 WN-1465-03-15-011 75 (3x25) 1600 x 800 x 500 3
BKDZN-87,5 WN-1465-03-16-011 87.5 (1x12.5)+(3x25) 1900 x 800 x 500 4
BKDZN-100 WN-1465-03-17-011 100 (2x25)+(1x50) 1600 x 800 x 500 3
BKDZN-112,5 WN-1465-03-18-011 112.5 (1x12.5)+(2x25)+(1x50) 1900 x 800 x 500 4
BKDZN-125 WN-1465-03-19-011 125 (1x25)+(2x50) 1600 x 800 x 500 3
BKDZN-150 WN-1465-03-20-011 150 (1x25)+(1x50)+(1x75) 1600 x 800 x 500 3
BKDZN-175 WN-1465-03-21-011 175 (1x25)+(3x50) 1900 x 800 x 500 4
BKDZN-200 WN-1465-03-22-011 200 (1x25)+(2x50)+(1x75) 1900 x 800 x 500 4
BKDZN-225 WN-1465-03-23-011 225 (1x25)+(1x50)+(2x75) 1900 x 800 x 500 4
BKDZN-250 WN-1465-03-24-011 250 (2x50)+(2x75) 1900 x 800 x 500 4
BKDZN-275 WN-1465-03-25-011 275 (1x50)+(3x75) 1900 x 800 x 500 4
BKDZN-300 WN-1465-03-26-011 300 (4x75) 1900 x 800 x 500 4
BKDZN-65 WN-1465-03-27-011 90 (2x12.5)+(1x25)+15 1900 x 800 x 500 4
BKDZN-90 WN-1465-03-28-011 140 (1x65)+(3x25) 1900 x 800 x 500 4


Attribute Value
Catalogue number 3760